Description
EcoSolutions Profile:
Recyclability Rate of the Product acc. to EN45555:
Design for Closing Resource Loops – Standard EN45555 – 80.7 %
ABB Site Meeting Group Waste To Landfill Target:
No non-hazardous waste is sent to a landfill
Extended Product Lifetime:
Product Durability
Offered with Takeback Services:
Take Back for Recycling
End Of Life Disassembling Instructions:
Environmental Product Declaration – EPD:
Technical
Dielectric Test Voltage:
50 / 60 Hz – 1 min 2 kV
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 25 kA
(400 V AC) 15 kA
(440 V AC) 15 kA
(230 V) 25 kA
(400 V) 15 kA
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 7.5 kA
Power Supply Connection:
Arbitrary
Contact Position Indication:
Red ON / Green OFF
Energy Limiting Class:
3
Electrical Endurance:
20000 AC cycle
Mechanical Endurance:
20000 cycle
Number of Protected Poles:
2
Number of Poles:
2P
Tightening Torque:
2.8 N·m
Screw Terminal Type:
Failsafe Bi-directional Cylinder-lift Terminal
Actuator Marking:
I / O
Actuator Material:
Insulation Group II, Black, Sealable
Recommended Screw Driver:
Pozidriv 2
Accessories Available:
Yes
Connecting Capacity:
Busbar 10/10 mm²
Flexible with Ferrule 0.75 … 25 mm²
Flexible 0.75 … 25 mm²
Flexible 0.75 … 25 mm²
Rigid 0.75 … 35 mm²
Rigid 0.75 … 35 mm²
Stranded 0.75 … 35 mm²
Installation Size:
acc. to DIN 43880 1
Terminal Type:
Screw Terminals
Actuator Type:
Toggle
Electrical
Tripping Characteristic:
C
Rated Operational Voltage:
acc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 440 V AC
Operational Voltage:
Maximum (Incl. Tolerance) 125 V DC
Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Minimum 12 V DC
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp):
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Input Voltage Type:
AC/DC
Rated Current (In):
2 A
Rated Short-Circuit Capacity:
(AC) 10 kA
(230 V AC) 10 kA
Rated Conditional Short-Circuit Current (Inc):
(230 V) 15 kA
(400 V) 25 kA
Frequency (f):
50 Hz
Rated Frequency (f):
50 / 60 Hz
Power Loss:
3.6 W
at Rated Operating Conditions per Pole 1.8 W
Overvoltage Category:
III
I²t Characteristic:
Design
Housing Material:
Insulation Group II, RAL 7035
Technical UL/CSA
Maximum Operating Voltage UL/CSA:
125 V DC
480Y/277 V AC
Interrupting Rating acc. to UL1077:
(125 V DC) 10 kA
(277 V AC) 6 kA
(480Y / 277 V AC) 6 kA
Connecting Capacity UL/CSA:
Busbar 14-8 AWG
Conductor 14-4 AWG
Tightening Torque UL/CSA:
18 in·lb
Material Compliance
RoHS Declaration:
RoHS Information:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Date:
20260312
REACH Declaration:
REACH Information:
False – does not contain substances > 0.1 mass percentage
REACH Date:
20260312
Conflict Minerals Reporting Template (CMRT):
Toxic Substances Control Act – TSCA:
SCIP:
9008497a-14f6-4cfd-83c5-11cf3bc660d1 Germany
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B:
Business To Business
Environmental
Ambient Air Temperature:
Operation -25 … +55 °C
Storage -40 … +70 °C
Reference Ambient Air Temperature:
30 °C
Degree of Protection:
IP20
IP40
Enclosure with Cover IP40
Pollution Degree:
3
Environmental Conditions:
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Resistance to Vibrations:
20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz
Resistance to Shock acc. to IEC 60068-2-27:
25g 2 shocks 13 ms
Dimensions
Width in Number of Modular Spacings:
2
Product Net Width:
35 mm
Product Net Height:
88 mm
Product Net Depth / Length:
69 mm
Product Net Weight:
0.224 kg
Pole Net Weight:
0.125 kg
Built-In Depth (t2):
69 mm
Dimension Diagram:
Engineering
EPLAN Data:
Ordering
Package Level 1 Units:
carton 5 piece
Package Level 1 Gross Weight:
1.16 kg
E-Number (Finland):
3210793
E-Number (Norway):
1665236
E-Number (Sweden):
2101220
Certificates and Declarations
Declaration of Conformity – CE:
Declaration of Conformity – UKCA:
Installation
Instructions and Manuals:
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position:
any
Popular Downloads
Data Sheet, Technical Information:
External Classifications and Standards
ETIM 9:
EC000042 – Miniature circuit breaker (MCB)
ETIM 10:
EC000042 – Miniature circuit breaker (MCB)
UNSPSC:
39121603
eClass:
V11.0 : 27141901
IDEA Granular Category Code (IGCC):
4897 >> Miniature circuit breakers
Object Classification Code:
F
Standards:
IEC/EN 60898-1
CSA 22.2 No. 235
IEC/EN 60947-2
UL 1077
Certification Agency:
EN
IEC
Standardization Body:
EN
IEC








Reviews